How to Read a Motor Nameplate

# How to Read a Motor Nameplate The nameplate is the motor's contract with the world — every number on it has a specific purpose, and most sizing mistakes start with ignoring one of them. ## The core fields **Rated power** (hp or kW): the *shaft* output at rated conditions — not electrical input, not peak capability. All comparisons start here. **Voltage and frequency**: rated at, say, 460 V 60 Hz. Motors tolerate ±10% voltage but suffer above it; running a 60 Hz motor on 50 Hz cuts speed 17% and cooling with it. **Full-load amps (FLA)**: the current at rated output and voltage. Conductors, overload heaters and breakers size from this number — from the NEC table value for the design, or the nameplate for the specific motor (nameplate wins for overloads; table wins for conductors per code). **RPM**: the full-load speed (e.g. 1,750 rpm for a "1,800 rpm" four-pole motor — synchronous speed minus slip). Speed sets the torque-per-horsepower relationship and the pump or fan curve it drives. **Service factor (SF)**: allowed continuous overload under rated conditions — 1.15 means the motor may run 15% over rated output. Not license for permanent overload: insulation life pays for it. ## The efficiency fields **Efficiency (η)**: shaft output ÷ electrical input at rated load — typically 85–96% for modern motors. Use it in every input-power and generator-sizing calculation. **Power factor (PF)**: the ratio of real to apparent power at rated load, typically 0.80–0.90. It determines kVA — what cables, switches and generators must carry. **Code letter**: locked-rotor kVA per horsepower, the key to starting surge. Code G ≈ 5.6–6.3 kVA/hp; multiply by hp for the exact inrush your generator or starter must fund. ## Design and insulation **Design letter** (A–E): the torque-speed curve family — NEMA Design B is the everyday workhorse with moderate starting torque. **Insulation class** (A/B/F/H) sets the winding temperature ceiling; each class step above rated temperature roughly halves insulation life, which is why thermal margin matters more than any other longevity factor. **Frame size**: mechanical mounting dimensions per NEMA or IEC standards — the field that decides whether the replacement bolts in. ## Putting it to work Nameplate η and PF feed the HP-to-amps, amps-to-HP and HP-to-kVA calculators; FLA checks against estimated full-load current; the code letter sizes the generator. A five-minute nameplate reading replaces hours of guessing.
← What Size Generator for a Motor? How Much Horsepower to Tow? →