What Size Generator for a Motor?
# What Size Generator for a Motor?
Motors are the hardest loads for generators: they draw surges at startup that dwarf their running rating. Size from the electrical load, not the horsepower badge, and size for the start.
## Step 1: Running kVA
Shaft horsepower converts to electrical input through efficiency, then to apparent power through power factor:
**kVA = HP × 0.7457 ÷ (η × PF)**
A 50 hp motor at η 0.92, PF 0.85 presents about **47.6 kVA** running — note how both loss terms push the number above the naive 37 kW.
## Step 2: Starting surge
Induction motors draw **6–8× rated current** at locked rotor for a fraction of a second to a few seconds. The generator must supply the surge without collapsing voltage, or the motor fails to accelerate, the breaker trips, and every other load on the bus browns out. Sizing rules of thumb:
- **Across-the-line (DOL) start**: 2–3× running kVA
- **Soft starter**: ~1.5–2× running kVA
- **VFD**: ~1.2× running kVA (the drive limits inrush)
Our 50 hp example with a DOL start: 47.6 × 2.5 ≈ **119 kVA** — the running number would have suggested a 60 kVA set, and it would fail every morning.
## Step 3: The rest of the load
Add every other load that may run simultaneously — lighting, controls, pumps — at their kVA, and check that the motor start occurs when the rest of the load is worst-case. Generators also derate for altitude (about 3% per 1,000 ft above 3,300 ft) and temperature; remote sites need the derate applied before sizing.
## Step 4: Verification habits
- Ask for the motor's **code letter** (locked-rotor kVA/hp) from the nameplate — it turns the 6–8× folklore into an exact figure for that motor.
- Prefer **reduced-voltage starting** on sets near the margin; a soft starter often saves a whole generator size class.
- Remember **power factor correction** cuts running kVA but not starting surge — capacitors help the bill, not the start.
## Quick reference
| Motor hp | Running kVA (η .92, PF .85) | DOL sizing |
|---|---|---|
| 10 | 9.5 | 20–25 kVA |
| 25 | 23.8 | 50–60 kVA |
| 50 | 47.6 | 100–125 kVA |
| 100 | 95.3 | 200–250 kVA |
The HP-to-kVA calculator computes the first column from your motor's actual nameplate values.