Ton of Refrigeration to HP Calculator
Chiller and AC sizing in the units the industry actually uses.
Formula
Source / basis: Refrigeration ton definition
The ton is a rate, not a weight
A "ton of refrigeration" descends from melting one short ton of ice over 24 hours: 12,000 BTU/hr of heat absorption. Nothing weighs two tons when your "2-ton AC" runs — it moves 24,000 BTU/hr. The unit survives because the whole HVAC trade thinks in it.
Electrical input depends on COP: a 3-ton system at COP 3.5 draws about 3.0 kW. That input — not the 10 mechanical-equivalent hp of heat — is what your breaker and bill see.
Cooling tons to power (COP 3.5)
| Tons | Cooling kW | Input kW | BTU/hr |
|---|---|---|---|
| 1 | 3.52 | 1 | 12,000 |
| 2 | 7.03 | 2.01 | 24,000 |
| 3 | 10.55 | 3.01 | 36,000 |
| 5 | 17.58 | 5.02 | 60,000 |
| 10 | 35.17 | 10.05 | 120,000 |
| 25 | 87.92 | 25.12 | 300,000 |
Worked Example
A 3-ton chiller at COP 3.5.
- Cooling = 3 × 3.517 ≈ 10.55 kW
- Input = 10.55 ÷ 3.5 ≈ 3.0 kW
- Heat-equivalent hp = 3 × 4.716 ≈ 14.1 hp (moved, not consumed)
Related Calculators
Frequently Asked Questions
Why does input power look so small against the "hp"?
The mechanical-equivalent hp describes heat moved, not electricity consumed. A heat pump multiplies input power by the COP — that is the entire point of refrigeration machinery.
What COP should I assume?
Check the unit's EER or SEER: COP ≈ EER ÷ 3.412. Seasonal ratings run lower than peak, so budget with the season-adjusted value.