Ton of Refrigeration to HP Calculator

Chiller and AC sizing in the units the industry actually uses.

tons
COP 3.5 ≈ EER 12. Modern splits: 3–4.5; chillers: 4–6.

Formula

1 ton = 12,000 BTU/hr = 3.517 kW · Input kW = cooling kW ÷ COP

Source / basis: Refrigeration ton definition

The ton is a rate, not a weight

A "ton of refrigeration" descends from melting one short ton of ice over 24 hours: 12,000 BTU/hr of heat absorption. Nothing weighs two tons when your "2-ton AC" runs — it moves 24,000 BTU/hr. The unit survives because the whole HVAC trade thinks in it.

Electrical input depends on COP: a 3-ton system at COP 3.5 draws about 3.0 kW. That input — not the 10 mechanical-equivalent hp of heat — is what your breaker and bill see.

Cooling tons to power (COP 3.5)

TonsCooling kWInput kWBTU/hr
13.52112,000
27.032.0124,000
310.553.0136,000
517.585.0260,000
1035.1710.05120,000
2587.9225.12300,000

Worked Example

A 3-ton chiller at COP 3.5.

  1. Cooling = 3 × 3.517 ≈ 10.55 kW
  2. Input = 10.55 ÷ 3.5 ≈ 3.0 kW
  3. Heat-equivalent hp = 3 × 4.716 ≈ 14.1 hp (moved, not consumed)
Values here are for general reference. Exact conversions are unit arithmetic; estimated quantities carry the stated error margins. Verify critical decisions against manufacturer data.

Frequently Asked Questions

Why does input power look so small against the "hp"?

The mechanical-equivalent hp describes heat moved, not electricity consumed. A heat pump multiplies input power by the COP — that is the entire point of refrigeration machinery.

What COP should I assume?

Check the unit's EER or SEER: COP ≈ EER ÷ 3.412. Seasonal ratings run lower than peak, so budget with the season-adjusted value.