Electric Motor Horsepower Calculator

From volts and amps to shaft horsepower — the electrician's everyday conversion.

V
A
%

Formula

3φ: HP = √3 × V × I × η × PF ÷ 746

Source / basis: Three-phase power relation

Reading the nameplate first

Motor nameplates state rated power, voltage, full-load current, service factor, efficiency and power factor — everything this calculator needs. Measured voltage and current at load, combined with nameplate η and PF, estimate actual shaft power: valuable for spotting motors running hot or severely underloaded.

Underloading wastes money: induction motors lose efficiency and power factor below about 60% load, so a 50 hp motor loafing at 20 hp costs more per delivered horsepower than a right-sized 25 hp unit.

√3 — where it comes from

In a balanced three-phase system, total power is three times the per-phase power. The line current in a wye (or delta) connection relates to phase values through √3, and the factors combine into the compact √3 × V(line) × I(line) form. It is bookkeeping, not magic — and omitting it is the most common mistake in three-phase sizing.

Shaft HP from current (400 V 3φ, η 92%, PF 0.85)

AmpsHPkW
53.632.71
107.275.42
1510.98.13
2518.1613.54
4029.0621.67
6043.5932.51

Worked Example

15 A measured on a 400 V three-phase motor.

  1. Input VA = √3 × 400 × 15 = 10,392
  2. Input watts × η × PF = 10,392 × 0.92 × 0.85 ≈ 8,126 W
  3. HP ≈ 10.9 hp (≈ 8.1 kW shaft)
Values here are for general reference. Exact conversions are unit arithmetic; estimated quantities carry the stated error margins. Verify critical decisions against manufacturer data.

Frequently Asked Questions

Why does my measured horsepower differ from the nameplate?

Nameplate numbers apply at rated load, rated voltage and rated temperature. Voltage sag, phase imbalance and part-load operation all shift the real values. A 5–10% deviation is normal.

Can I run a motor above nameplate power?

Briefly, within the service factor (usually 1.15). Sustained overload shortens insulation life — every 10°C above rated cuts it roughly in half.

Does this work for VFD-driven motors?

Roughly, but VFD output waveforms make clamp meters misreport true RMS unless rated for them. Use a drive-rated meter or read the drive's own power output.