VRF System HP to Tons of Refrigeration
VRF "HP" naming decoded into engineering units.
Formula
Source / basis: VRF/VRV industry naming convention
A third HP convention, just for VRF
Variable-refrigerant-flow systems — marketed as VRV by their inventor — carry system sizes like "10 HP", "16 HP", "20 HP". Unlike split-AC retail labels (9,000 BTU/hr each), VRF system-HP classes run near 10,000 BTU/hr, and unlike either, the class descends from the outdoor-unit compressor bank. Mixing the three conventions across documents is why VRF schedules so often confuse reviewers.
Indoor-unit total capacity can exceed outdoor capacity by 100–130% (heat-recovery diversity), so check whether the figure quoted is outdoor or connected-indoor capacity before converting.
Common VRF system sizes
| System HP | BTU/hr | TR | kW cooling |
|---|---|---|---|
| 6 HP | 60,000 | 5 | 17.58 |
| 8 HP | 80,000 | 6.67 | 23.45 |
| 10 HP | 100,000 | 8.33 | 29.31 |
| 16 HP | 160,000 | 13.33 | 46.89 |
| 20 HP | 200,000 | 16.67 | 58.61 |
| 30 HP | 300,000 | 25 | 87.92 |
Worked Example
A "16 HP" VRF heat-recovery system.
- Capacity = 16 × 10,000 = 160,000 BTU/hr
- Tons = 160,000 ÷ 12,000 ≈ 13.3 TR
- Cooling kW ≈ 46.9 — outdoor capacity; connected indoor units may total more
Related Calculators
Frequently Asked Questions
Is VRF HP the same as split-AC HP?
No — different conventions (10,000 vs 9,000 BTU/hr) and different scopes (outdoor system vs single unit). Convert both to BTU/hr before comparing.
Why can indoor capacity exceed outdoor?
Diversity: not all zones peak simultaneously. Heat-recovery VRF shifts capacity between heating and cooling zones instead of dumping it — that flexibility is the product's main selling point.