Fan Horsepower Calculator
Moving air costs power too — CFM and static pressure define the bill.
Formula
Source / basis: Standard fan power relation (imperial)
The fan laws — why speed changes everything
Three affinity laws govern every fan: airflow scales with speed, pressure with speed squared, and power with speed cubed. Halving fan speed cuts airflow 50%, pressure 75% — and power to just 12.5%. That cube is why variable-speed drives on fans save so much energy, and why overspeeding a fan to fix a ventilation shortfall explodes motor load.
System curves, not fan curves alone
Static pressure depends on the duct system: filters clog, dampers close, coils foul. A fan selected for 1.5 in. w.g. may face 2.5 after filter loading, riding up its curve to lower flow and higher power. Good designs carry a safety margin in pressure — and cleanable filters.
Brake HP at 65% fan efficiency
| CFM | SP (in. w.g.) | BHP |
|---|---|---|
| 1,000 | 0.5 | 0.12 |
| 2,500 | 1 | 0.61 |
| 5,000 | 1.5 | 1.82 |
| 10,000 | 2 | 4.84 |
| 20,000 | 3 | 14.52 |
Worked Example
5,000 CFM against 1.5 in. w.g.
- AHP = 5000 × 1.5 ÷ 6356 ≈ 1.18 hp
- BHP = 1.18 ÷ 0.65
- BHP ≈ 1.81 hp — a 2 hp motor at standard speed
Related Calculators
Frequently Asked Questions
Why did power rise so much after we added filters?
Pressure rose, and power scales with CFM × SP. If flow also rose on the fan curve, the cube law compounds it. Re-check the operating point against the new system curve.
Does this cover total pressure or static?
The 6356 relation uses static pressure, the convention for fan selection. Total-pressure versions exist but differ little for low-velocity systems.