Fan Horsepower Calculator

Moving air costs power too — CFM and static pressure define the bill.

CFM
in. w.g.
%
Axial 45–65%; backward-curved centrifugal 65–80%.

Formula

AHP = CFM × SP ÷ 6356 · BHP = AHP ÷ η_fan

Source / basis: Standard fan power relation (imperial)

The fan laws — why speed changes everything

Three affinity laws govern every fan: airflow scales with speed, pressure with speed squared, and power with speed cubed. Halving fan speed cuts airflow 50%, pressure 75% — and power to just 12.5%. That cube is why variable-speed drives on fans save so much energy, and why overspeeding a fan to fix a ventilation shortfall explodes motor load.

System curves, not fan curves alone

Static pressure depends on the duct system: filters clog, dampers close, coils foul. A fan selected for 1.5 in. w.g. may face 2.5 after filter loading, riding up its curve to lower flow and higher power. Good designs carry a safety margin in pressure — and cleanable filters.

Brake HP at 65% fan efficiency

CFMSP (in. w.g.)BHP
1,0000.50.12
2,50010.61
5,0001.51.82
10,00024.84
20,000314.52

Worked Example

5,000 CFM against 1.5 in. w.g.

  1. AHP = 5000 × 1.5 ÷ 6356 ≈ 1.18 hp
  2. BHP = 1.18 ÷ 0.65
  3. BHP ≈ 1.81 hp — a 2 hp motor at standard speed
Values here are for general reference. Exact conversions are unit arithmetic; estimated quantities carry the stated error margins. Verify critical decisions against manufacturer data.

Frequently Asked Questions

Why did power rise so much after we added filters?

Pressure rose, and power scales with CFM × SP. If flow also rose on the fan curve, the cube law compounds it. Re-check the operating point against the new system curve.

Does this cover total pressure or static?

The 6356 relation uses static pressure, the convention for fan selection. Total-pressure versions exist but differ little for low-velocity systems.