HP to kVA Calculator
Generator sizing starts here: apparent power, not shaft power.
Formula
Source / basis: kW = hp × 0.7457; kVA = kW ÷ PF
Why kVA and not kW
Generators and transformers heat with total current, including the reactive component that does no work. kVA captures that full burden; kW counts only the useful part. A 50 hp motor at η 0.92, PF 0.85 presents about 47.6 kVA of apparent load even though its shaft converts 37.3 kW.
Motor starting complicates everything: induction motors draw 6–8× rated current at locked rotor, and voltage-sag during starting can stall other loads. Generator vendors size with starting-kVA rules — typically 2–3× running kVA for across-the-line starts, less with soft starters or VFDs.
Running kVA (η 92%, PF 0.85)
| HP | kW input | kVA |
|---|---|---|
| 10 | 8.11 | 9.54 |
| 25 | 20.26 | 23.84 |
| 50 | 40.53 | 47.68 |
| 100 | 81.05 | 95.36 |
| 200 | 162.11 | 190.72 |
Worked Example
A 50 hp motor.
- Input kW = 37.3 ÷ 0.92 ≈ 40.5
- kVA = 40.5 ÷ 0.85
- kVA ≈ 47.6 running — a 100–125 kVA set for across-the-line starting
Related Calculators
Frequently Asked Questions
What kVA generator for one motor?
Running kVA is the floor; starting surge decides. Rule-of-thumb: 2–3× running kVA for direct-on-line starts, ~1.5× with a soft starter, ~1.2× with a VFD.
Does power correction help generator sizing?
Yes — capacitors raise PF, cutting kVA for the same kW. On generator-fed sites the savings can be a whole size class.