HP to kVA Calculator

Generator sizing starts here: apparent power, not shaft power.

hp
%

Formula

kVA = HP × 0.7457 ÷ (η × PF)

Source / basis: kW = hp × 0.7457; kVA = kW ÷ PF

Why kVA and not kW

Generators and transformers heat with total current, including the reactive component that does no work. kVA captures that full burden; kW counts only the useful part. A 50 hp motor at η 0.92, PF 0.85 presents about 47.6 kVA of apparent load even though its shaft converts 37.3 kW.

Motor starting complicates everything: induction motors draw 6–8× rated current at locked rotor, and voltage-sag during starting can stall other loads. Generator vendors size with starting-kVA rules — typically 2–3× running kVA for across-the-line starts, less with soft starters or VFDs.

Running kVA (η 92%, PF 0.85)

HPkW inputkVA
108.119.54
2520.2623.84
5040.5347.68
10081.0595.36
200162.11190.72

Worked Example

A 50 hp motor.

  1. Input kW = 37.3 ÷ 0.92 ≈ 40.5
  2. kVA = 40.5 ÷ 0.85
  3. kVA ≈ 47.6 running — a 100–125 kVA set for across-the-line starting
Values here are for general reference. Exact conversions are unit arithmetic; estimated quantities carry the stated error margins. Verify critical decisions against manufacturer data.

Frequently Asked Questions

What kVA generator for one motor?

Running kVA is the floor; starting surge decides. Rule-of-thumb: 2–3× running kVA for direct-on-line starts, ~1.5× with a soft starter, ~1.2× with a VFD.

Does power correction help generator sizing?

Yes — capacitors raise PF, cutting kVA for the same kW. On generator-fed sites the savings can be a whole size class.