Amps to HP Calculator
Clamp meter in hand: what horsepower is this motor actually producing?
Formula
Source / basis: Electrical power relations, inverted
Field measurements to shaft power
A clamp meter plus the nameplate efficiency and power factor turns electrical measurements into a shaft-power estimate — useful for spotting overloaded or underloaded motors. Compare the result with the nameplate: running below 50% load wastes efficiency, running above 100% shortens insulation life.
Accuracy depends entirely on using the real efficiency and power factor. Nameplate values apply at rated load; at half load the power factor of an induction motor can fall by 0.15 or more, so treat light-load estimates as rough.
Shaft HP from measured current (230 V 1φ, η 90%, PF 0.85)
| Amps | HP |
|---|---|
| 5 | 1.18 |
| 10 | 2.36 |
| 15 | 3.54 |
| 20 | 4.72 |
| 30 | 7.08 |
| 40 | 9.44 |
Worked Example
20 A measured on a 230 V single-phase motor.
- Input watts = 20 × 230 × 0.90 × 0.85 = 3,519 W
- HP = 3,519 × 0.90... (efficiency already applied) ÷ 745.7
- HP ≈ 4.7 hp — likely a 5 hp motor running near rated load
Related Calculators
Frequently Asked Questions
Why does the result come out low for my motor?
Most often the power factor at actual load is below the nameplate value, or voltage is sagging. Both push real current up and make the estimated hp read low.
Can I use this to verify a pump upgrade?
As a trend tool, yes — record current before and after; the ratio tracks the power ratio. For contractual verification, use a torque transducer or calibrated dyno.