HP to Amps Calculator

Size the breaker and the wire: how many amps does this motor draw?

hp
V
%
Typical 0.8–0.9 for induction motors at load.

Formula

1φ: I = HP × 745.7 ÷ (V × η × PF) · 3φ: I = HP × 745.7 ÷ (√3 × V × η × PF)

Source / basis: Electrical power relations

Why efficiency and power factor matter

Shaft horsepower is what the motor delivers; the supply must fund everything lost on the way. An 85% efficient motor drawing reactive magnetising current pulls meaningfully more amps than the naive watts-per-volt division suggests. Ignoring the efficiency and power-factor terms undersizes wire and breakers — the classic cause of nuisance tripping on long cable runs.

Three-phase supplies share the load across three conductors, so the current per leg is only 1/√3 (about 58%) of the single-phase equivalent at the same voltage — the reason industrial motors cluster on three-phase power.

Full-load amps, single-phase 230 V, η 90%, PF 0.85

HPAmps (230 V 1φ)Amps (400 V 3φ)
14.241.41
28.482.81
312.714.22
521.197.03
1042.3814.07
2084.7628.14

Worked Example

A 5 hp single-phase motor on 230 V.

  1. Input watts = 5 × 745.7 = 3,728 W ÷ (0.90 × 0.85) = 4,876 VA
  2. I = 4,876 ÷ 230
  3. I ≈ 21.2 A — expect a 30 A circuit in practice
Values here are for general reference. Exact conversions are unit arithmetic; estimated quantities carry the stated error margins. Verify critical decisions against manufacturer data.

Frequently Asked Questions

Should I size the breaker exactly to this current?

No — breakers protect conductors and must tolerate motor inrush (6–8× full-load current for a second or two). Use NEC motor tables and their dedicated motor-circuit rules; this calculator sizes your understanding, not the breaker.

Why is my measured current higher than calculated?

Voltage sag under load, a lower-than-nameplate power factor at part load, and mechanical overload all raise current. Values more than ~15% above calculation deserve investigation.

Does this apply to DC motors?

Roughly — for DC use I = P ÷ (V × η) with no power factor. The three-phase formula does not apply.