HP to Amps Calculator
Size the breaker and the wire: how many amps does this motor draw?
Formula
Source / basis: Electrical power relations
Why efficiency and power factor matter
Shaft horsepower is what the motor delivers; the supply must fund everything lost on the way. An 85% efficient motor drawing reactive magnetising current pulls meaningfully more amps than the naive watts-per-volt division suggests. Ignoring the efficiency and power-factor terms undersizes wire and breakers — the classic cause of nuisance tripping on long cable runs.
Three-phase supplies share the load across three conductors, so the current per leg is only 1/√3 (about 58%) of the single-phase equivalent at the same voltage — the reason industrial motors cluster on three-phase power.
Full-load amps, single-phase 230 V, η 90%, PF 0.85
| HP | Amps (230 V 1φ) | Amps (400 V 3φ) |
|---|---|---|
| 1 | 4.24 | 1.41 |
| 2 | 8.48 | 2.81 |
| 3 | 12.71 | 4.22 |
| 5 | 21.19 | 7.03 |
| 10 | 42.38 | 14.07 |
| 20 | 84.76 | 28.14 |
Worked Example
A 5 hp single-phase motor on 230 V.
- Input watts = 5 × 745.7 = 3,728 W ÷ (0.90 × 0.85) = 4,876 VA
- I = 4,876 ÷ 230
- I ≈ 21.2 A — expect a 30 A circuit in practice
Related Calculators
Frequently Asked Questions
Should I size the breaker exactly to this current?
No — breakers protect conductors and must tolerate motor inrush (6–8× full-load current for a second or two). Use NEC motor tables and their dedicated motor-circuit rules; this calculator sizes your understanding, not the breaker.
Why is my measured current higher than calculated?
Voltage sag under load, a lower-than-nameplate power factor at part load, and mechanical overload all raise current. Values more than ~15% above calculation deserve investigation.
Does this apply to DC motors?
Roughly — for DC use I = P ÷ (V × η) with no power factor. The three-phase formula does not apply.