Motor Full-Load Amps Calculator

Approximate full-load current before you reach for the code book.

hp
V
Common motor voltages: 230, 460, 575 (N. America); 400 (EU).

Formula

FLA ≈ HP × 746 ÷ (√3 × V × η × PF)

Source / basis: NEC-style approximation

Why the NEC table beats any formula

NEC Table 430.250 lists measured-average FLA for standard motor designs at each horsepower and voltage — the product of decades of fleet data. Individual motors differ ±10%, and premium-efficiency designs run lower. Use this estimate for planning; use the table (or the nameplate) whenever a code calculation depends on it.

Estimated FLA — three-phase

HP230 V460 V
12.391.2
24.782.39
511.955.98
1023.9111.95
2559.7729.88
50119.5359.77
100239.06119.53

Worked Example

A 10 hp motor at 460 V three-phase.

  1. FLA ≈ 10 × 746 ÷ (√3 × 460 × 0.90 × 0.87)
  2. FLA ≈ 12.4 A — NEC 430.250 lists 14 A for this class; size conductors per the table
Values here are for general reference. Exact conversions are unit arithmetic; estimated quantities carry the stated error margins. Verify critical decisions against manufacturer data.

Frequently Asked Questions

Which do I trust — this or the nameplate?

The nameplate, always, for that specific motor. Use estimates only before the motor is specified.

Why does NEC list higher values than my calculation?

The table embeds older, less efficient motor designs as the baseline — deliberately conservative so conductor sizing stays safe across the fleet.