HP to kW Calculator — Three Phase
Nameplate hp to what the supply must actually deliver.
Formula
Source / basis: Motor power relations
The two losses stacked between hp and the bill
Motor efficiency accounts for heat in the windings and iron; power factor accounts for reactive current the supply must carry without doing useful work. Both multiply the line current beyond the naive power calculation, and both appear on the nameplate — which is why nameplate-derived estimates beat guesswork.
Energy cost follows the input kW; cable and breaker sizing follow the amps. The calculator reports both so neither gets forgotten.
Input kW and current (400 V 3φ, η 92%, PF 0.85)
| HP | Input kW | Amps |
|---|---|---|
| 5 | 4.05 | 6.88 |
| 10 | 8.11 | 13.76 |
| 25 | 20.26 | 34.41 |
| 50 | 40.53 | 68.82 |
| 100 | 81.05 | 137.64 |
Worked Example
A 25 hp motor on 400 V three-phase.
- Shaft kW = 18.6; input = 18.6 ÷ 0.92 ≈ 20.3 kW
- Current = 20,264 ÷ (√3 × 400 × 0.85)
- I ≈ 34.4 A per line
Related Calculators
Frequently Asked Questions
Do I pay for reactive power?
Industrial tariffs usually charge demand in kVA or penalise low PF, so yes indirectly. Capacitor banks raise PF toward 0.95 to cut those charges.
Why is the current higher than hp ÷ (V × √3)?
That shortcut ignores efficiency and power factor. Real current runs 25–35% higher for typical motors — enough to trip an undersized breaker.